Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨ Join us at New York University for the AI Pitch Competition · April 2, 2026 · Apply Now ✨
EFI Logo
Contact Us
Back to Resources
Case StudyPower Generation & Distribution
Tata Power

Deploying Wireless E5 Sensors for Grid Resilience

Tata Power deployed Innvendt's E5 wireless sensor network across distribution substations to enable real-time fault current monitoring—transforming grid resilience from a reactive posture to a predictive one.

5 min readNovember 20, 2024
Primary Impact
72 hrs
Advance Fault Warning Time
72 hours avg.
Advance Warning Time
Average advance warning before fault condition—enabling planned rather than emergency maintenance
67% reduction
Unplanned Outages
Unplanned outages at monitored substations reduced by 67% in 12 months post-deployment
-58%
Customer Interruption Minutes
Customer interruption minutes at monitored substations reduced 58% year-over-year
40% reduction
Emergency Callouts
Emergency after-hours maintenance callouts reduced by 40% through proactive scheduling

The Challenge

Tata Power's distribution network serves millions of customers across multiple service territories. Unexpected transformer and feeder failures caused unplanned outages averaging 4.2 hours—each outage affecting tens of thousands of customers and generating regulatory scrutiny under reliability performance standards. The existing SCADA system detected faults only after protective devices operated, providing no advance warning of developing fault conditions. The operations team had no visibility into the health degradation that preceded failures, making maintenance scheduling reactive rather than predictive.

The Solution

Innvendt deployed E5 wireless sensors at 120 distribution substations, monitoring earth leakage current, earth resistance, and neutral current imbalance at transformer neutrals and earth grids. The Innvendt platform performs continuous trend analysis on all monitored channels, generating predictive alerts when degradation patterns consistent with developing fault conditions are detected. Alerts are classified by predicted time-to-failure and severity, enabling maintenance teams to prioritize response appropriately.

Implementation

Phased Deployment Across Substations

Deployment was executed in three phases, prioritizing the 40 highest-criticality substations (feeding hospital and industrial loads) in phase 1, followed by medium-criticality residential feeders in phases 2 and 3. Each substation installation required two to four sensors depending on transformer count and neutral configuration. Installation was designed for hot-work deployment, allowing sensors to be installed without substation de-energization during normal operations.

Fault Signature Training and Calibration

The Innvendt platform's fault prediction algorithms were calibrated to Tata Power's specific transformer fleet by analyzing historical SCADA fault records against retrospective sensor data from a 90-day pre-deployment monitoring period at 20 instrumented substations. This calibration identified the specific leakage current and earth resistance signatures that preceded transformer failures in Tata Power's network, enabling site-specific prediction models with false alarm rates below 5%.

Control Room Integration

Innvendt alert data was integrated into Tata Power's distribution management system (DMS) via a real-time data feed, displaying predictive health alerts alongside real-time SCADA data in the control room console. Control room operators received predictive alerts 48-72 hours before predicted fault conditions, enabling coordination with field crews for planned maintenance interventions without requiring emergency callouts.